The ultrasonic level meter is a digital level meter with a microprocessor controller. During the measurement, the ultrasonic pulse is emitted by the sensor (transducer), and the sound wave is reflected by the liquid surface and received by the same sensor. It is converted into an electrical signal by the piezoelectric crystal, and the distance from the sensor to the surface of the measured liquid is calculated by the time between the emission and reception of the sound wave. Due to the use of non-contact measurement, the measured medium is almost unlimited, and it can be widely used to measure the height of various liquids and solid materials.
There is a display, a sound, and the measured value jumps randomly or the value does not change with the distance:
The ultrasonic level meter is installed at a too large inclination;
The pulse intensity is improperly set;
It causes large residual vibration or diffraction;
There are more than two ultrasonic level meters working at the same time;
It causes mutual interference;
The electromagnetic interference on site is too large;
There are bubbles or debris on the liquid surface.
Adjust the sensor axis to be perpendicular to the target plane;
Generally, the range is within 1-3m, and the emission pulse intensity is 2-5;
Try to eliminate mutual interference;
Find the interference source and shield the interference;
Eliminate bubbles and debris on the liquid surface.
Common faults: The sensor makes a sound, and the display shows a blind area or exceeds the range:
Exceeding the range of the ultrasonic level meter;
The measuring surface is too close to the probe;
Improper use in high dust, high foam, high steam environment or the working temperature is too high or too low;
Improper pulse intensity setting.
Adjust the actual range of the ultrasonic level meter to within the working range of the instrument;
Adjust the application environment to the required range;
Modify the emission pulse intensity until the display is stable.
Common faults: 4-20mA output is abnormal; current output is too high, too low, and jumps.
Load resistance is too large;
The range “end point” is modified, and the output fine-tuning parameter “output low-end fine-tuning” or “output high-end fine-tuning” is modified;
Power supply rectification and filtering are not good;
Insufficient power-on time.
Reduce load resistance;
Re-adjust relevant parameters by yourself;
Replace a DC regulated power supply with a larger capacity;
Power on for >15 minutes to preheat.
Common faults: does not work after power on, no display, no sound from the sensor…
The power supply is not connected, or the positive and negative poles are connected in reverse;
The working voltage is too low, the instrument does not work, or the working voltage is too high, and the ultrasonic level meter is damaged.
Check the circuit and connect the wires according to the instructions.
Common faults: The ultrasonic level meter has a display and sound, but the number does not change with the distance.
The input working voltage is too low, and the ultrasonic level meter does not work properly;
The ultrasonic level meter sensor or power driver is damaged.
Use a 12-24V DC power supply.
Common faults: The control output does not work.
Incorrect parameter settings;
The external current limiting resistor is too large;
The external current limiting resistor is too small, and the ultrasonic level meter has been damaged.
Reset parameters;
Reduce the current limiting resistor.

In modern industries such as water treatment, oil & gas, agriculture, and manufacturing, accurate level measurement is critical for safety, automation, and cost control.
Pokcenser ultrasonic level sensors provide a high-precision, maintenance-free, and cost-effective solution for liquid and material level monitoring.
Whether you need tank level measurement, water depth monitoring, or harsh environment solutions, Pokcenser offers reliable products for global OEM/ODM projects.
Up to ±0.25% FS, ensuring precise measurement
Perfect for:
Corrosive liquids
High temperature tanks
Hazardous environments
Stable even with:
Foam
Vapor
Electromagnetic interference
No moving parts
Easy installation
Long service life
A compact and intelligent ultrasonic level transmitter designed for stable long-term operation.

4–20mA + RS485 output
Measuring range: 5m / 7m / 10m / 15m
Accuracy: 0.5% FS (0.25% customizable)
IP66 (IP68 optional)
Optional intrinsically safe explosion-proof
Non-contact measurement
Compact structure with high stability
Cost-effective for bulk projects
Full-range automatic temperature compensation
Intelligent anti-interference & error correction
Water tanks
Diesel fuel tanks
Reservoirs / rivers / lakes
Food industry
Wastewater treatment
Widely used as a fuel level sensor and industrial tank level transmitter.
Ultrasonic sensors are more cost-effective, while radar is better for extreme conditions like high pressure or heavy vapor.
Yes. The PWL-U500 is widely used for diesel tank level measurement due to its non-contact and safe design.
Temperature changes
Foam or vapor
Improper installation
Yes. Pokcenser provides full OEM/ODM customization.
Looking for a reliable ultrasonic level sensor supplier?
Contact Pokcenser today to get:
Fast quotation
Technical consultation
Custom solutions