When comparing industrial sensors, one of the first specifications engineers notice is accuracy.
Manufacturers often advertise specifications such as:
±0.5%FS
±0.2%FS
±0.1%FS
±0.075%FS
At first glance, these numbers may seem straightforward. However, many users misunderstand what these accuracy ratings actually mean and how they affect real-world measurements.
In this guide, we'll explain how sensor accuracy is defined, how to calculate measurement errors, and when investing in a higher-accuracy instrument makes sense.

Sensor accuracy describes how close a measured value is to the actual value.
No measurement instrument is perfectly accurate. Every sensor has some degree of error between the measured value and the true value.
For example:
If the actual pressure is:
10.0 bar
And the transmitter displays:
10.1 bar
The measurement error is:
0.1 bar
The smaller the error, the higher the accuracy.

Most industrial transmitters specify accuracy as a percentage of Full Scale (FS).
Full Scale refers to the maximum measurement range of the instrument.
Example:
Pressure transmitter range:
0-100 bar
Full Scale (FS):
100 bar
If the accuracy is:
±0.5%FS
The maximum error is:
100 × 0.5%
= ±0.5 bar
This means the transmitter may read:
9.5 bar
10.0 bar
10.5 bar
when the actual pressure is 10 bar.

Let's compare several common accuracy ratings using the same 0-100 bar pressure transmitter.
Accuracy | Maximum Error |
±0.5%FS | ±0.5 bar |
±0.2%FS | ±0.2 bar |
±0.1%FS | ±0.1 bar |
±0.075%FS | ±0.075 bar |
As accuracy improves, measurement uncertainty decreases.
This is especially important in applications requiring precise process control.
Many users assume that a ±0.5%FS transmitter has a 0.5% error regardless of the measured value.
This is incorrect.
Consider a transmitter with:
Range:
0-100 bar
Accuracy:
±0.5%FS
Maximum error remains:
±0.5 bar
Whether the measured pressure is:
10 bar
50 bar
90 bar
the error limit remains the same.
Actual pressure:
10 bar
Possible reading:
9.5-10.5 bar
Relative error:
5%
Actual pressure:
90 bar
Possible reading:
89.5-90.5 bar
Relative error:
0.56%
This is why selecting an appropriate measurement range is extremely important.
These two specifications are often confused.
Measures how close a reading is to the true value.
Measures how consistently a sensor produces the same reading under identical conditions.
Example:
A transmitter repeatedly measures:
50.1 bar
50.1 bar
50.1 bar
Excellent repeatability.
However, if the actual pressure is 49.5 bar, the accuracy is still poor.
A good industrial instrument should provide both high accuracy and good repeatability.
Another common misunderstanding involves resolution.
The smallest detectable change in a measurement.
Example:
A display showing:
50.01 bar
has higher resolution than a display showing:
50.0 bar
However, higher resolution does not automatically mean higher accuracy.
A sensor can display many decimal places while still having significant measurement error.

Different industries require different levels of accuracy.
Recommended Accuracy:
±0.5%FS
Suitable for:
Pump monitoring
Water distribution systems
General process control
Recommended Accuracy:
±0.2%FS to ±0.5%FS
Suitable for:
Water tanks
Wastewater tanks
Chemical storage tanks
Recommended Accuracy:
±0.1%FS to ±0.2%FS
Suitable for:
Dosing systems
Reactor monitoring
Process optimization
Recommended Accuracy:
±0.075%FS or better
Suitable for:
High-value processes
Energy applications
Precision industrial systems
Higher accuracy instruments generally cost more.
However, the additional investment may be justified when:
Small measurement errors can affect product consistency.
Accurate measurements improve control system performance.
Many industries must meet strict measurement standards.
Level measurement errors can affect inventory calculations.
The PWP3051DP Smart Monocrystalline Silicon Differential Pressure Transmitter offers accuracy up to ±0.075%FS, making it suitable for demanding industrial applications requiring high measurement precision.
Accuracy up to ±0.075%FS
Excellent long-term stability
HART communication
Suitable for liquid, gas, and steam measurement
Industrial-grade reliability
Process control systems
Chemical plants
Power generation
Water treatment facilities
Industrial automation systems
Lower-cost instruments may not provide the precision required for critical applications.
Not every application needs ±0.075%FS performance.
For many water and wastewater systems, ±0.5%FS is sufficient.
An incorrectly selected range can have a greater impact than the accuracy specification itself.
Accuracy should be evaluated together with stability and drift performance.
Pokcenser provides industrial measurement solutions for customers in more than 100 countries.
Our product portfolio includes:
Pressure Transmitters
Differential Pressure Transmitters
Radar Level Sensors
Ultrasonic Level Sensors
Flow Meters
Water Quality Instruments
We help customers select the most cost-effective balance between performance, reliability, and accuracy.
Yes in terms of measurement precision, but not every application requires such high accuracy.
Generally yes, because higher-accuracy sensors require better sensing elements, calibration, and manufacturing processes.
FS stands for Full Scale, which refers to the maximum measurement range of the instrument.
For industrial process measurement, accuracy is usually more important than display resolution.
Chemical processing, power generation, pharmaceutical manufacturing, and precision industrial applications often require higher accuracy instruments.